Low voltage surge arresters with disconnector - PROTECT series New

Application:
Protect series surge arresters are designed to protect devices in low-voltage power systems against direct and indirect overvoltages and switching overvoltages. They are used primarily on low-voltage overhead lines. It is recommended that one set of arresters be installed at a distance of no more than 500 m along the entire length of the line.

The arresters meet the requirements of the following standards: IEC-EN 61643-11 and LVD 2014/35/EU (dated 26.02.2014).
Construction and advantages:
  • UV-resistant, non-flammable housing (V-0)
  • Grounding disconnector with visual fault indicator
  • Equipped with an M8 screw for connecting line terminals
  • High degree of protection
  • Wide selection of additional accessories
Protect limiter characteristics:
  • Nominal mains voltage: 230/400 V
  • Continuous operating voltage Uc: according to the table
  • Line discharge class: II
  • Type: T2, A
  • Nominal discharge current In: 5 kA or 15 kA
  • Maximum discharge current Imax: for In = 5 kA Imax = 40 kA, for In = 15 kA Imax = 50 kA
  • Short circuit resistance: ≥4.5 kA
  • Humidity: up to 95%
  • Energy absorption capacity [kJ/1kV Uc]: according to the table
  • Operating temperature range: -40°C to +85°C
  • Mains frequency: 48 to 62 Hz
  • Maximum installation altitude: 2000 m above sea level
  • Pollution zone: III (according to PN-E 06303:1998)

Electrical data:

SymbolContinuous operating voltage
UC [V]
Nominal discharge current
In [kA]
Max discharge current
Imax [kA]
Voltage protection level
Up [V]
Energy absorption capacity
Uc [kJ/1kV UC]
Protect 2-5-D 280 5 40 ≤ 900 ≥ 3
Protect 4-5-D 440 5 40 ≤ 1400 ≥ 3
Protect 5-5-D 500 5 40 ≤ 1700 ≥ 3
Protect 6-5-D 660 5 40 ≤ 2000 ≥ 3
Protect 2-15-D 280 15 50 ≤ 900 ≥ 5
Protect 4-15-D 440 15 50 ≤ 1400 ≥ 5
Protect 5-15-D 500 15 50 ≤ 1700 ≥ 5
Protect 6-15-D 660 15 50 ≤ 2000 ≥ 5

Attachment:

Product catalog Poland
Sicame Group product catalog
Installation instructions

Contact us

+48 22 622 64 01
Sicame Polska Sp. z o.o.
Puławska 366
02-819 Warszawa

Electrical data:

SymbolContinuous operating voltage
UC [V]
Nominal discharge current
In [kA]
Max discharge current
Imax [kA]
Voltage protection level
Up [V]
Energy absorption capacity
Uc [kJ/1kV UC]
Protect 2-5-D 280 5 40 ≤ 900 ≥ 3
Protect 4-5-D 440 5 40 ≤ 1400 ≥ 3
Protect 5-5-D 500 5 40 ≤ 1700 ≥ 3
Protect 6-5-D 660 5 40 ≤ 2000 ≥ 3
Protect 2-15-D 280 15 50 ≤ 900 ≥ 5
Protect 4-15-D 440 15 50 ≤ 1400 ≥ 5
Protect 5-15-D 500 15 50 ≤ 1700 ≥ 5
Protect 6-15-D 660 15 50 ≤ 2000 ≥ 5