Insulation piercing clamp for surge arresters T1 PROTECT New

Application::
It is used to make electrical connections between insulated conductors of the main LV line (Al or Cu) and surge arresters (branch).

Construction:
  • The body is made of glass fibre reinforced polyamide with high mechanical strength and resistance to weather conditions
  • Dielectric resistance 6 kV/1 min. in water – class 1
  • On the main line side: protection against water ingress into the insulated conductor by means of a waterproof seal
  • On the branch side: socket for connecting a surge arrester
  • Easy to assemble and safe to use
  • A bolt with a shear head provides a tightening torque. Once the head shears, the bolt can be unscrewed
  • Compliance with the standard: PN-EN 50483-4:2009


Symbol Main line cross section
[mm2]
Branch
Stopper Socket
Torsion screw Breaking moment
[Nm]
Snap-off head cap Head size
[mm]
Dimensions
[mm]
T1 PROTECT 16-120 M8 1 x M6 9±1 13 42 x 24 x 87

Attachment:

Product catalog Poland
Sicame Group product catalog
Installation instructions

Contact us

+48 22 622 64 01
Sicame Polska Sp. z o.o.
Puławska 366
02-819 Warszawa
Symbol Main line cross section
[mm2]
Branch
Stopper Socket
Torsion screw Breaking moment
[Nm]
Snap-off head cap Head size
[mm]
Dimensions
[mm]
T1 PROTECT 16-120 M8 1 x M6 9±1 13 42 x 24 x 87