APR 160 and APR 400 disconnector

They are used to protect low voltage lines. The device is both a disconnector and a fuse. The design allows the disconnector to be operated from the ground thanks to the operating rod.

APR 160-X vs APR 400-X Table
Model APR160-X APR400-X
Rated switching voltage [V] 415 500
Number of poles 1, 3, 4 1, 3, 4
Nominal frequency 50 Hz 50 Hz
Rated insulation voltage 1000V 1000V
Rated impulse voltage 6 kV 12 kV
Rated continuous current [A] 160A 400A
Nominal current for armature 160A 400A
Rated switching current 160A 400A
Conventional thermal current 160A 400A
Conventional short circuit current 50kA 100kA
Rated work continuous continuous
Category of use AC22B AC22B
Fuse link size NH00 NH1 NH2
Degree of contamination PD3 PD3
Degree of protection IP23 IP23
Connected cross-sections Al/Cu wires 2 x (16-150mm²) 2 x (50-240mm²)
Connection durability 200 link 200 joints
Mechanical durability 1600 cycles 1600 cycles

X – number of poles (1, 3 or 4).
The disconnectors comply with the standards: PN-EN 60947-3 and PN-EN 60947-1

Fuse switches

Sicame Polska product catalog
Sicame Group product catalog
Assembly instructions part 1
Assembly instructions part 2
leaflet_Detachable_bridges_issue 1-2018 (1).pdf
leaflet_Detachable Bridges_issue 1-2018 (2).pdf
leaflet_Detachable_bridges_issue 1-2018 (3).pdf
leaflet_Detachable Bridges_issue 1-2018.pdf

Contact us

+48 22 622 64 01
Sicame Polska Sp. z o.o.
Puławska 366
02-819 Warszawa

Strona korzysta z plików cookies w celu realizacji usług i zgodnie z Polityką Plików Cookies. Możesz określić warunki przechowywania lub dostępu do plików cookies w Twojej przeglądarce. Korzystanie z naszych serwisów internetowych bez zmiany ustawień dotyczących cookies oznacza, że będą one zapisane w pamięci urządzenia.

This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.